Operation Profile
An Operation Profile defines emergency recipients, test calls, alarm contacts and the controller connection for a Gateway.
Assign and apply a profile
- Select the installation’s Organization and Device type → EDGE-GW. Enter the emergency numbers and match the alarm contacts to the installed wiring.
- Enable the profile. Select it during registration or assign it under Devices → Gateway → Settings and save.
- Check Actions, then verify the profile and version on the Gateway. To retry, use Tools → Update operation profile in Connect or Operation Profile → Refresh profile from server on the Gateway.
The Gateway stores the applied profile locally and sends relevant settings to each Display. Verify changes to numbers and contacts on the device.
Identity and availability
| Field | Meaning |
|---|---|
| Profile name, Description | Label and notes used to choose the profile. Name on the Gateway is the internal record ID. |
| Organization, Device type | Determine where the profile is available. Choose EDGE-GW for a Gateway. |
| Enabled | Makes the profile selectable. New profiles start disabled. Emergency calling is configured separately. |
| Version | Read-only revision assigned when an enabled profile is saved. |
Emergency calls and automatic tests
| Field | Behavior |
|---|---|
| Phone 1, Phone 2, Phone 3 | The Gateway tries numbers in order, skips blanks and repeats until the operator acknowledges with 0. |
| Time to cancel call | Timeout in seconds per number attempt. A missing or nonpositive value gives five minutes per attempt. |
| Time to test call | Hours between automatic tests. Default 72 hours when missing. 0 or less disables automatic tests. |
| Test call phone | Receiving Gateway’s number. Automatic calls require this number. |
Cabin alarm filter
The filter applies to the cabin button wired to the Smart Display’s MicroMatch input. Buttons on the Gateway’s digital and MicroMatch inputs always use a 3-second hold.
Set the filter on the profile’s Emergency Phone tab. Connect shows the saved values under Emergency config.
| Setting | Effect |
|---|---|
| Enable COP alarm filter | Off by default. Allows a longer hold during confirmed normal passenger travel. Disable during maintenance or repair. Connect label: COP alarm filter enabled. |
| Alarm Filter Bypass (seconds) | Total continuous hold from the initial press. Use 3–30 whole seconds, default 3. Connect label: Alarm filter bypass. |
The longer hold applies only while fresh controller data confirms normal travel and changing car position. A stopped car (including doors open at a landing), maintenance, an unknown state, or stale or missing movement data uses 3 seconds.
Example. With a 10-second bypass, holding throughout travel triggers the alarm at 10 seconds. If the car stops after five seconds with the button still held, it triggers when the Display detects the stop. Releasing resets the timer.
Alarm inputs, display, and controller
| Setting | Field use |
|---|---|
| Gateway MicroMatch contact, Digital input contact, Display MicroMatch contact | Set each contact to its actual resting state. An unset direction disables that input. |
| Display standby time | Minutes, with 0 disabled. Current Display builds store the setting but do not yet enter standby automatically. |
| Controller type, Controller IP | Select none, core or mpk411 for the installed system. Support depends on the installed software. Enter the controller’s local IP address. |
| Custom | Advanced JSON field, unused by current Gateway and Display builds. |
Normally open contacts close when activated. Normally closed contacts open when activated.